Commercial (UL/CSA)

UL 1478

Additional Details

APPLIANCE WIRING MATERIAL
Style 1478 Single conductor cable using non-integral jacket
Rating 60 deg C, 30 Vac, Cable flame.
Conductor 30 AWG minimum.
Insulation Labeled or complying with Manufacture’s AWM Procedure.
Covering Optional – a fibrous wrap, serving or braid; Paper; Nylon; oriented Polyethylene terephthalate; or a thermoplastic-tape wrap.
Shield Optional, over twisted assembly or any group of cables, non-ferrous metallic braid or wrap.
Jacket Extruded PVC.
Diameter of cable under jacket Minimum average thickness Minimum thickness at any point
0.425 inch or less 30 mils 23 mils
0.426-0.700 inch 45 mils 36 mils
0.701-1.000 inch 60 mils 48 mils
Standard Appliance Wiring Material UL 758.
Marking General.
Use External interconnect of electronic equipment.
UL and the UL Logo are trademarks of UL LLC © 2014