Commercial (UL/CSA)

UL 2786

Additional Details

APPLIANCE WIRING MATERIAL
Style 2786 Multiple-conductor cable using non-integral jacket.
Rating 60 deg C, Voltage not specified, Horizontal flame.
Insulation Labeled or complying with Manufacturer’s AWM Procedure.
Assembly Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. the conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
Shield Optional.
Covering (Optional) – A 6 mil or heavier extruded PVC covering may be over the conductor assembly.
Jacket Extruded PVC;
major dia in inches of 0.250 or less 15 mils minimum average thickness 12 mils minimum thickness at any point
0.251-0.700 dia 30 avg 24 min
0.701-1.000 dia 60 avg 48 min
1.001-1.500 dia 80 avg 64 min.
– Major diameter if cable is flat or oval
Standard Appliance Wiring Material UL 758.
Marking General.
Use Internal wiring.
UL and the UL Logo are trademarks of UL LLC © 2014


If you don’t find what you’re looking for please contact us. The cable designs in this listing represent our standard product line. If you require special modifications or unique designs, SCC can create special cables for the most demanding applications. For custom applications please contact us.