UL 1011
Additional Details
WIRING MATERIAL
Style 1011 Single Conductor with Extruded Insulation
Rating 80 deg C, 600 Vac or 750 Vdc, Horizontal flame. Optional – 60 deg C or 80 deg C Oil.
Conductor 30 AWG – 2000 kcmil, Solid or Stranded.
Insulation Extruded PVC.
Conductor size Minimum average thickness Minimum thickness at any point
30-9 AWG 30 mils 27 mils
8-7 AWG 45 mils 40 mils
6-2 AWG 60 mils 54 mils
1-4/0 AWG 80 mils 72 mils
250-500 kcmil 95 mils 86 mils
550-1000 kcmil 110 mils 99 mils
1100-2000 kcmil 125 mils 112 mils
Standard Appliance Wiring Material UL 758.
Marking General. Tags may indicate the following: 2500 Volts Peak – For Electronic Use Only.